Skripsi
OPTIMASI PEMECAHAN BEBAN PENYULANG DEWANTARA TERHADAP DROP TEGANGAN DAN SUSUT DAYA MENGGUNAKAN SIMULASI ETAP 19.0.1 DI PT. PLN (PERSERO) UP3 OGAN ILIR
The Dewantara Feeder of the Prabumulih Substation is a 20 kV distribution network of PT. PLN (Persero) UP3 Ogan Ilir with a medium-voltage overhead line (SUTM) extending 152.37 km, which experiences voltage drops and power losses exceeding the standard limits when delivering energy to customers. This study aims to analyze the reduction of power losses and voltage drops under existing conditions and after optimization through feeder load splitting using ETAP 19.0.1 simulation with the Simple Additive Weighting (SAW) optimization method. The simulation results show a significant decrease in voltage drop, from 17.2% in the existing condition to 7.8% after optimization, while power losses did not show significant changes since they remained below the 5% threshold. The SAW method identified the optimal switching point in segment B with the highest score of 0.812. These results indicate that feeder load splitting can effectively reduce feeder loading and can be recommended to PT. PLN (Persero) UP3 Ogan Ilir to prevent overloading, particularly in segments with large industrial loads and long, high-density lines.