ANALISA EFEKTIVITAS PENULANGAN BALOK PILECAP DAN PELAT LANTAI STRUKTUR INTAKE AKIBAT VARIASI BEBAN GETAR POMPA (STUDI KASUS INTAKE POMPA KARANGANYAR PULOKERTO)
This study aims to analyze the reinforcement efficiency of pilecap beams and floor slabs subjected to variations in pump-induced vibration loads in the Karanganyar Pulokerto Pump Intake Structure. The analysis was carried out using ETABS software with the Walking Vibration Analysis method on two types of centrifugal pumps, namely EN 733 and DPV 18-60. The evaluation was based on vertical acceleration (Accel Z), peak acceleration, the resulting Demand/Capacity Ratio (DCR), structural deflection, and reinforcement requirements. The results indicate that the EN 733 pump generated a greater vibration response than the DPV 18-60 pump, with maximum DCR values of 1.869 and 1.139, respectively, for the existing 0.20 m thick floor slab. Based on the peak acceleration capacity of 490.33 mm/s², the existing slab did not satisfy the serviceability requirements. Variations in slab thickness showed that a 0.35 m thick slab was able to achieve DCR values below 1.0 under all loading conditions, thereby satisfying the serviceability criteria against pump-induced vibrations. In addition, all pilecap beams satisfied the allowable deflection requirements and reinforcement provisions in accordance with SNI 2847:2019. Therefore, a 0.35 m thick floor slab can be considered the most effective configuration for reducing vibration responses in the analyzed intake structure.